Space completed using the one and only technology

with the sole aim to make the future happier and healthier.

Ceiling Type

Ceiling Cassette Type(AFC-CA TYPE)

  • Space efficiency through the concealed installation in the ceiling
  • Evenly discharge in 2 directions
  • Discharged air flow controllable by season
Evenly discharge in 2 directions
  • Thanks to the down-flow method, the air current distribution is good, and you can control the discharged air flow by seasons.
Functions
  • Air volume control in high, middle and low levels
  • Powerless speed control using contact points
  • Automatic operation according to the temperature change and centralized control using the wired remote controller optional
Features
  • Excellent indoor space efficiency
    The compactly designed main body is buried in the ceiling. Because it does not occupy the floor area, you can use the indoor space more efficiently.
  • Easy installation and maintenance
    By installing the grille panel in line with the ceiling surface, you can reduce the construction cost.
    Thanks to the natural water drainage, there is no device with complex functions, making maintenance easy.
  • AC motor
    The condenser-operated single-phase induction motor has low noise and long life.

Drawings

Standard Specifications

Item Unit AFC-02CA AFC-03CA AFC-04CA AFC-06CA AFC-08CA
Capacity Capacity condition A B A B A B A B A B
Cooling capacity W 3,150 2,160 4,280 2,830 5,730 4,050 7,990 5,520 11,080 7,907
Kcal/h 2,710 1,860 2,680 2,430 4,930 3,480 6,870 4,750 9,530 6,800
Heating capacity W 5,790 3,490 8,010 4,770 10,800 6,730 14,650 9,100 21,310 12,950
Kcal/h 4,980 3,000 6,890 4,100 9,290 5,790 12,600 7,830 18,330 11,140
Flow rate ℓ/min 9.0 6.3 12.3 8.1 16.4 11.6 22.9 15.8 31.8 22.7
Loss of head mAq 0.5 0.3 1.4 0.8 3.0 1.7 5.1 5.1 5.2 2.9
Blower Type Sirocco Fan
Dimension mm Ø192 x 170 L Ø192 x 200 L Ø192 x 170 L Ø192 x 200 L
Air volume ㎥/min 5.7 8.5 11.3 17 22.6
Operate   Direct motor operate
Quantity EA 1 1 2 2 3
Motor Type Semi-sealed type (6 poles and class B insulation)
Power consumption W 45 55 75 95 55+95
Quantity EA 1 1 1 1 2
Heat exchanger Type Multi-Pass  Cross  Finned  Tube( Super Slit  Fin)
Fin Pitch mm 2.1
Piping Inlet A  20A (PF 3/4")
Outlet A  20A (PF 3/4")
Drain mm Ø16(outer diameter)
Exterior materials galvanized steel/powder coating
Heat insulation and sound-absorbing material P.E & P.U Foam
Air volume control Control switch in high, middle and low levels
Power Single phase/220V/60Hz
Air filter Vinyl chloride (water cleaning type)
Equipment weight Kg 23 27 33 39 47
1. Capacity condition A

The cooling capacity is for indoor air DB 27℃ and WB 21℃ and inlet water temperature 5℃, and the heating capacity is for indoor air 18℃ and inlet water temperature 80℃.

2. Capacity condition B

The cooling capacity is for indoor air DB 27℃ and WB 19.5℃ and inlet water temperature 7℃, and the heating capacity is for indoor air 21℃ and inlet water temperature 60℃.