Space completed using the one and only technology

with the sole aim to make the future happier and healthier.

Ceiling Type

High Static Pressure Ceiling-concealed Type(AFC-CH TYPE)

  • Most effective on a site where the length of the duct connected to the equipment is long (high static pressure)
    (5-8mmAq external static pressure)
  • Burial installation in the ceiling for indoor space efficiency
  • Various models available and capacity selectable according to the installation space (9 models)
  • High-efficiency BLDC motor requires less power consumption than the AC motor
Simultaneous cooling and heating of multiple rooms
  • With installation of the multidrop chamber and spiral duct (tin duct or flexible duct), it is possible to cool and heat multiple indoor spaces.
Variable speed port(V.S.P)
  • The duct-connected product may create unpleasant noise due to excessive air volume. Here, you can control the air volume of the product.
Functions
  • Air volume control in high, middle and low levels
  • Powerless speed control using contact points
  • Automatic operation according to the temperature change and centralized control using the wired remote controller optional
Features
  • Excellent indoor space efficiency
    The compactly designed main body is buried in the ceiling. Because it does not occupy the floor area, you can use the indoor space more efficiently.
  • Easy installation and maintenance
    The slim equipment does not occupy a large space. It is fully buried, supplying air through the duct, which makes luxurious and clean interior design possible.
    Thanks to the natural water drainage, there is no device with complex functions, making maintenance easy.
  • BLDC motor
    The brush-less DC motor minimizes operational noise and power consumption.
  • Air purification function optional
    You can install an air purifier of the photocatalyst, UV lamp, or ionizer type for sterilization, antibacterial actions, deodorization, or removal of the sick house syndrome to create a pleasant indoor environment.

Drawings

Standard Specifications

* Since AFC 16CH is a large-capacity product, there is no flexible supply of headers in the form of sockets.
Item Unit AFC-05CH AFC-06CH AFC-08CH AFC-10CH AFC-12CH AFC-14CH AFC-16CH AFC-18CH AFC-20CH
Capacity Capacity condition A B A B A B A B A B A B A B A B A B
Cooling capacity W 5,500 5,020 7,407 5,523 10,030 7,510 11,990 8,920 14,330 10,720 15,810 12,240 23,300 17,540 25,400 19,070 27,450 20,590
Kcal/h 4,730 4,320 6,370 4,750 8,630 6,460 10,310 7,670 12,320 9,220 13,600 10,520 20,040 15,080 21,850 16,400 23,610 17,710
Heating capacity W 10,760 7,430 14,530 8,880 18,630 11,240 22,400 13,430 25,035 16,150 29,800 18,470 42,150 25,560 46,220 27,980 45,760 30,350
Kcal/h 9,250 6,390 12,500 7,640 16,020 9,670 19,270 11,550 21,530 13,890 25,630 15,890 36,250 21,980 39,750 24,070 39,360 26,100
Flow rate ℓ/min 15.8 14.4 21.2 15.8 28.8 21.5 34.4 25.6 41.1 30.7 45.3 35.1 66.8 50.3 72.8 54.7 78.7 59.0
Loss of head mAq 5.5 3.1 9.1 5.1 5.2 2.9 8.2 4.5 6.1 3.4 7.4 4.1 8.0 4.6 9.6 5.4 11.2 6.2
Blower Type Sirocco Fan
Dimension mm Ø200 x 190 L
Air volume ㎥/min 14 17 23 28 34 40 45 51 57
Operate   Direct motor operate
Quantity EA 1 2 2 3 3 3 4 4 4
Motor Type Semi-sealed type (6 poles and class B insulation)
Power consumption W 80 55 92 134 161 177 182 246 348
Quantity EA 1 1 1 2 2 2 2 2 2
Heat exchanger Type Multi-Pass  Cross  Finned  Tube(Super Slit  Fin)
Fin Pitch mm 2.1
Piping Inlet A  20A (PF 3/4") 25A (PT 1" )
Outlet A  20A (PF 3/4") 25A (PT 1" )
Drain A Nipple 20A (PT 3/4")
Exterior materials galvanized steel
Heat insulation and sound-absorbing material P.E & P.U Foam
Air volume control Control switch in high, middle and low levels
Power Single phase/220V/60Hz
Air filter Vinyl chloride (water cleaning type)
Equipment weight Kg 19 22 25 30 41 46 48
1. Capacity condition A

The cooling capacity is for indoor air DB 27℃ and WB 21℃ and inlet water temperature 5℃, and the heating capacity is for indoor air 18℃ and inlet water temperature 80℃.

2. Capacity condition B

The cooling capacity is for indoor air DB 27℃ and WB 19.5℃ and inlet water temperature 7℃, and the heating capacity is for indoor air 21℃ and inlet water temperature 60℃.