Space completed using the one and only technology

with the sole aim to make the future happier and healthier.

Ceiling Cassette Type

1-way Cassette Type(AFC-C1 TYPE)

Features
  • Suitable for bedrooms and small spaces with the uni-directional air discharge
  • Suitable for residential buildings with a low ceiling height and residential environments where it is hard to install the inspection cover
  • Grille panel design selectable according to the room interior design
  • Automatic ID assignment function, capable of linked operation through various central controls
  • Power interruption compensation function
  • High head/low noise drain pump
  • Automatic filter replacement alarm function optional
Silent operation

The low-power high-efficiency BLDC motor is used for energy cost reduction. The cross fan is used for even air distribution and low noise, for a quiet and pleasant room environment.

Compact design

The ultra-light slim-type design makes it possible to install the product in a space with a low ceiling height and provides high space efficiency.

Grille panel design selectable according to the room interior design

You can select a panel pattern according to the indoor interior design and space characteristics.

Selectable inspection hole size optional

You can select the standard or large-sized inspection hole according to the spatial characteristics. The inspection cover is separable for easy maintenance.

Detachable inspection cover optional

The 1-way type does not need a separate inspection cover, reducing the equipment cost, and maintenance is easy by removing the inspection covers.

Freezing and rupture prevention function

The piping circulation mode operates in linkage when the room temperature is not greater than 5℃ (hot water supply, circulation, automatic valve signal)/p>

Drawings

Standard Specifications

Item Unit AFC-01C1 AFC-02C1 AFC-03C1 AFC-04C1
Capacity Capacity condition A B A B A B A B
Cooling capacity W 3,660 2,500 4,250 3,000 4,650 3,610 5,580 4,590
Kcal/h 3,150 2,150 3,650 2,580 4,000 3,100 4,800 3,950
Heating capacity W 5,815 3,720 7,070 4,360 8,900 5,230 9,830 6,160
Kcal/h 5,000 3,200 6,080 3,750 7,650 4,500 8,450 5,300
Flow rate ℓ/min 10.5 7.5 12.1 8.6 13.3 10.3 16.0 13.2
Loss of head mAq 2.41 1.40 3.13 1.76 3.78 2.13 4.40 2.64
Blower Type Cross Flow Fan
Dimension mm Ø96 x 785 L
Air volume ㎥/min 7 9 11 14
Operate   Direct motor operate
Quantity EA 1
Motor Type Semi-sealed type (8 poles and class B insulation), BLDC Motor
Power consumption W 29 40 56 77
Quantity EA 1
Heat exchanger Type Multi-Pass  Cross  Finned  Tube(Super Slit  Fin)
Fin Pitch mm 2.1
Piping Inlet A 20A (PF 3/4") 
Outlet A 20A (PF 3/4") 
Drain mm Ø16 (outer diameter)/drain up pump embedded type (8W)/head 600mm (based on the outlet)
Exterior materials Main body: ABS/Grille panel: ABS
Heat insulation and sound-absorbing material Poly Ethylene Foam + Styrofoam
Air volume control Turbo, high, middle, low, automatic remote controller (wired remote control optional)
Power Single phase/220V/60Hz
Air filter Vinyl chloride (water cleaning type)
Discharge swing motor DC 12V Stepping Motor
Main body dimensions mm 410(W) x 970(D) x 125(H)
Grille panel dimensions mm 470(W) x 1,160(D) x 35(H)
Equipment weight Kg 15
1. Capacity condition A

The cooling capacity is for indoor air DB 27℃ and WB 21℃ and inlet water temperature 5℃, and the heating capacity is for indoor air 18℃ and inlet water temperature 80℃.

2. Capacity condition B

The cooling capacity is for indoor air DB 27℃ and WB 19.5℃ and inlet water temperature 7℃, and the heating capacity is for indoor air 21℃ and inlet water temperature 60℃.